STUDI PENENTUAN TINGKAT ISOLASI DASAR TRANSFORMATOR MELALUI SIMULASI NUMERIK

Master Theses from #PUBLISHER# / 2006-09-25 09:37:25
Oleh : Wasimudin Surya Saputra, S2 - Electrical Engineering
Dibuat : 2002-02-00, dengan 1 file

Keyword : "

basic insulation level, pro-rated, numeric model, EA/ TP.



Bila suatu peralatan listrik seperti transformator daya mengalami modifikasi, maka boleh jadi tingkat isolasi dasar (TID) dari peralatan tersebut juga mengalami perubahan. Berapa besar nilai TID yang baru ini cukup sulit untuk ditentukan.




Menurut standar IEC, TID suatu peralatan didefinisikan sebagai ketahanan isolasi peralatan terhadap harga puncak impuls tegangan surja 1,2/50 ,us. Akan tetapi untuk transformator daya yang mengalami modifikasi, standar ini tidak mungkin diterapkan mengingat pada transformator daya pengujian impuls merupakan pengujian jenis (type test), artinya hanya dapat dilakukan pada sampel dan merupakan pengujian merusak.




Pada tulisan ini diajukan suatu metode untuk mengestimasi TID transformator daya melalui simulasi numerik Untuk keperluan tersebut dibuat suatu pro-rated transformator satu fasa dengan belitan tegangan rendah dan tegangan tinggi masing-masing terdiri dari 24 lilitan. Model numerik kondisi transien pro-rated ini divalidasi dengan basil eksperimen penerpaan tegangan impuls dari sumber generator hibrid 3 kV 1,2/50 ,us. Dari hasil eksperimen dan sinnrlasi EMTP diharapkan diperoleh suatu model rnarrerik yang dapat dipergunakan untuk mengeva/uasi TID pro-rated transfonnator ini dan dapat diberlakukan pada transformator yang sebenarnya.



Deskripsi Alternatif :

Abstract :



If an electrical equipment like power transformers has a modification, maybe the Basic Insulation Level (BIL) of the equipment mentioned will be changed. To decide the new value of the BIL is very complicated.




According to the IEC Standards, the BIL of an equipment is defined as an insulation strength of equipment against peak value of impulse voltage 1,2/50 ps. However, for the modified power transformers, the Standard is impossible to apply because the impulse test on power transformers is type test. It means that it can be done on the sample and it is considered as the destruction test.




This paper describes a method to estimate the BIL of power transformers through numeric simulation. For the need mentioned, a pro-rated of single phase transformers is made. This pro-rated consists of high and low voltage winding which has 24 turns each. The numeric model which represented transient conditions of this pro-rated is validated with the result of the impulse voltage application experiment from the hybrid generator 3 kV 1,2/50 ps source. In the hope of getting a numeric model that can be used to evaluate the BIL of this pro-rated and it can he used to the real transformers, the result of experiment and EAITP simulation are compared.




Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTITBPP
OrganisasiS2 - Electrical Engineering
Nama KontakUPT Perpustakaan ITB
AlamatJl. Ganesha 10
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon62-22-2509118, 2500089
Fax62-22-2500089
E-mail Administratordigilib@lib.itb.ac.id
E-mail CKOinfo@lib.itb.ac.id

Print ...

Kontributor...

  • Pembimbing 1 :
    Parouli M Pakpahan,Dr.,Ir .

    Pembimbing 2 :
    Bambang Anggoro,Ir.,M Sc.

    Scan:
    Mudjiono
    25-09-2006)

    , Editor: mudjiono@#publisher#

File PDF...