Path: Top > S1-Final Project > Electrical Power Engineering-STEI > 2017

STUDI TAHANAN KONTAK PADA SAMBUNGAN BATERAI DENGAN PENGATURAN TEKANAN KONTAK SERTA KETEBALAN PELAPISAN PERAK, ZINC, DAN NIKEL PADA SAMBUNGAN

Undergraduate Theses from JBPTITBPP / 2017-10-05 11:12:50
Oleh : NELSON POETRA YOGA HADISOESENO (NIM. 18011018), S1 - Electrical Power Engineering-STEI
Dibuat : 2017-10-05, dengan 1 file

Keyword : kontak konduktor, sambungan, pelapisan, tebal pelapisan, tekanan kontak, tahanan, rugi-rugi daya

Tugas akhir ini membahas tahanan kontak pada sambungan konduktor tembaga dengan variasi material pelapisan, ketebalan pelapisan, dan tekanan kontak. Penelitian ini dilatarbelakangi oleh kenyataan bahwa sambungan memiliki tahanan yang berperan penting bagi kinerja sambungan elektrik dalam menyalurkan energi listrik. Sambungan yang baik adalah sambungan yang memiliki tahanan sekecil mungkin sehingga rugi-rugi daya dan keandalan sambungan juga akan kecil.



Pada penelitian ini digunakan sampel sambungan material tembaga tanpa pelapis, sambungan tembaga dengan pelapisan zinc, sambungan tembaga dengan pelapisan nikel, dan sambungan tembaga dengan pelapisan perak. Pertama dilakukan pengukuran tahanan dengan pengujian tanpa pembebanan pada setiap sampel dengan variasi tekanan kontak 5.6, 7.0, dan 8.4 MPa. Kemudian dilakukan pengukuran tahanan pada pembebanan dengan variasi arus searah 9, 18, dan 27 A serta variasi tekanan kontak yang sama. Semua pengukuran ini dilakukan dengan ketebalan pelapisan 5, 15, dan 25 μm.



Hasil penelitian menunjukkan bahwa sampel sambungan tembaga dengan pelapisan perak dan ketebalan pelapisan 5 μm memiliki tahanan serta rugi-rugi daya yang jauh lebih kecil dibandingkan sampel sambungan tembaga lainnya.

Deskripsi Alternatif :

This thesis studies about contact resistance on copper conductor contact relative to plating materials, plating thickness, and contact pressure. This study is important because conductor contact plays an important role on electric distribution performance. A good conductor contact would have low contact resistance, low energy losses and better reliability.



In this study, the sample that going to be tested are conductor contact without plating, conductor contact with zinc plating, conductor contact with nickel plating, and conductor contact with silver plating. First aspect that is going to be tested is contact resistance measurement without load on each. The next test is contact resistance and temperature measurement with DC load of 9, 18, and 27 A. Each test is conducted with the contact pressure variation of 5.6, 7.0, dan 8.4 MPa, and with plating thickness of 5, 15, and 25 μm.



The result shows that conductor contact with 5 μm silver plating have much lower contact resistance and lower energy losses compared to all the other configuration.

Copyrights : Copyright (c) 2001 by Perpustakaan Digital ITB. Verbatim copying and distribution of this entire article is permitted by author in any medium, provided this notice is preserved.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTITBPP
OrganisasiS1 - Electrical Power Engineering-STEI
Nama KontakUPT Perpustakaan ITB
AlamatJl. Ganesha 10
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon62-22-2509118, 2500089
Fax62-22-2500089
E-mail Administratordigilib@lib.itb.ac.id
E-mail CKOinfo@lib.itb.ac.id

Print ...

Kontributor...

  • Pembimbing : Dr. Umar Khayam ST. MT, Editor: Alice Diniarti

File PDF...