SISTEM PROTEKSI PETIR PADA JARINGAN TEGANGAN MENENGAH AKIBAT INDUKSI SAMBARAN DEKAT YANG DIPICU OLEH ROKET BERKAWAT

INDUCED VOLTAGE ON MEDIUM OVERHEAD LINE CAUSED BY NEARBY STRIKE FROM ROCKET TRIGGERED LIGHTNING

Undergraduate Theses from JBPTITBPP / 2017-09-27 15:37:42
Oleh : Krismanto Eka Widodo, S2 - Electrical Engineering
Dibuat : 2017-09-05, dengan 1 file

Keyword : Multi Chamber Arrester (MCA), Saluran Udara Tegangan Menengah (SUTM) 20kV, Roket berkawat, Petir, Induksi

Permasalahan teknis pada Penyulang Hercules PLN Area Karawang salah satunya adalah gangguan petir. Tingginya kerapatan petir (5,5 sambaran/km2/tahun) di daerah Jatiluhur menyebabkan ganguan petir menjadi salah satu faktor penyebab seringnya trip recloser BBK dan CLN. Gangguan petir ini akan menyebabkan tegangan lebih pada jaringan distribusi, gangguan ini disebabkan oleh sambaran langsung dan sambaran tidak langsung. Pada penelitian ini akan dilakukan pemasangan teknologi arrester dengan inovasi baru yaitu Multi Chamber Arrester (MCA) dengan menggunakan celah udara dan tekanan udara pada ruangan sebagai teknologinya. MCA ini memiliki fungsi untuk melindungi saluran udara dari induksi petir, khususnya pada saluran udara tegangan menengah 20 kV.Sistem proteksi MCA akan diuji dengan petir dari hasil pemicuan roket berkawat yang berjarak 81 m dari Penyulang Hercules PLN Area Karawang. Perhitungan dan analisa akibat sambaran tidak langsung akan dilakukan pada penelitian ini dengan menggunakan persamaan Rusck. Hasil perhitungan dan analisa menunjukkan performa MCA mampu menghentikan arus puncak akibat induksi petir mencapai 16 kA dan perbandingan hasil performa MCA dilakukan pada PLN Area Serpong menunjukkan performa MCA dapat menurunkan gangguan 36% di Penyulang Ruko setelah pemasangan dua tahun.

Deskripsi Alternatif :

One of technical problem on the Hercules Feeder at PLN Karawang area is lightning disturbances. The high lightning density (5.5 stroke / km2 / year) in Jatiluhur Area caused lightning disturbanceand can be one of the factors caused trip of BBK and CLN recloser frequently. This lightning disturbance will cause more overvoltage on the distribution line, this disturbance can be either direct strike and indirect strike. In this research will be installed of new arrester with new innovation technology that is Multi Chamber Arrester (MCA) that used air gap and air pressure in the chamber as its technology. The MCA has a function to protect overhead lines from lightning, especially 20 kV medium voltage. The MCA protection system will be tested by rocket triggered lightning, the rocket platform is 81 meters from the Hercules Feeder in PLN Karawang Area. Calculation and analysis due to indirect strike will be done in this research by using Rusck method. The results of the calculation and analysis shows the performance of MCA capable to stop the peak current due to lightning induction current up to 16 kA and the comparison of MCA performance result has done at PLN Serpong Area and shows the MCA performance can reduce 36% line fault of Ruko Feeder after two years MCA installed.

Copyrights : Copyright (c) 2001 by Perpustakaan Digital ITB. Verbatim copying and distribution of this entire article is permitted by author in any medium, provided this notice is preserved.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTITBPP
OrganisasiS
Nama KontakUPT Perpustakaan ITB
AlamatJl. Ganesha 10
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon62-22-2509118, 2500089
Fax62-22-2500089
E-mail Administratordigilib@lib.itb.ac.id
E-mail CKOinfo@lib.itb.ac.id

Print ...

Kontributor...

  • Prof. Dr. Dipl. Ing. Ir. Reynaldo Zoro, Editor: Irwan Sofiyan

File PDF...