ANALISIS KINERJA ISOLATOR KERAMIK DENGAN PELAPISAN RTV SILICONE RUBBER UNTUK PENGGUNAAN AREA PANTAI STUDI KASUS: PANTAI PANGANDARAN

PERFORMANCE ANALYSIS OF CERAMIC INSULATOR WITH RTV SILICONE RUBBER COATING FOR COASTAL AREA APPLICATION. CASE STUDY: PANGANDARAN COASTAL AREA

Master Theses from JBPTITBPP / 2017-09-27 15:37:42
Oleh : DINI FAUZIAH (NIM: 23215091), S2 - Electrical Engineering
Dibuat : 2017-09-27, dengan 1 file

Keyword : Isolator keramik, penuaan area pantai, RTV silicone rubber coating.

Penelitian ini menganalisis pengaruh pelapisan Room Temperatur Vulcanized (RTV) silicone rubber terhadap kinerja isolator keramik tegangan distribusi 20 KV jenis pos pin untuk penggunaan di daerah pantai tropis. Pengujian dilakukan di GI Pangandaran, dengan memberikan penuaan alami selama lima tahun tujuh bulan sejak Oktober 2011 hingga pengukuran terakhir pada Mei 2017 terhadap enam buah isolator keramik dengan coating dan enam buah isolator keramik tanpa diberikan coating. Selama waktu penuaan tersebut isolator diberikan stress tegangan AC 50 Hz sebesar 11 kV. Selama penuaan, data diambil secara periodik berupa data arus bocor, sudut kontak, THD, dan suhu permukaan isolator. Pengambilan data dilakukan pada tiga waktu, yaitu pagi siang dan sore karena rata-rata pada setiap kondisi mempunyai karakteristik kelembaban dan temperatur yang berbeda sehingga dapat diketahui pada kondisi apa isolator paling mudah mengalami flashover. Dari data berupa bentuk gelombang arus bocor kemudian dapat ditentukan komponen harmonik yang muncul untuk selanjutnya dilakukan analisis terhadap karakteristik yang muncul dari isolator selama mengalami penuaan.


Setelah kedua jenis isolator mengalami penuaan selama 5 tahun 7 bulan, peneliti mengambil sampel isolator untuk dilakukan pengujian dengan tujuan mengetahui kinerja isolator pada kondisi kabut bersih dan kabut garam dengan kenaikan tegangan. Hasilnya adalah selama diberikan kabut bersih, kedua jenis isolator tidak mengalami flashover. Sedangkan pada pengujian dengan kabut garam, isolator non coating mengalami flashover pada tegangan 50 kV dan isolator yang telah diberi coating memiliki tegangan flashover yang lebih tinggi yaitu 60 kV.


Untuk mengetahui parameter apa yang mengalami perubahan selama penuaan isolator, dilakukan simulasi pada data hasil pengukuran di lapangan dengan parameter amplitude, bentuk gelombang dan THD yang muncul pada arus bocor selama penuaan. Berdasarkan seluruh hasil pengujian, didapat bahwa penggunaan coating dapat meningkatkan kinerja isolator keramik.

Deskripsi Alternatif :

This study analyzed the effect of Room Temperature Vulcanized (RTV) silicone rubber coating on ceramic pin post insulator performance of 20 kV for use in tropical coastal area. The test was conducted at Pangandaran Switchyard Area, by giving natural aging for five years seven months since first installing at October 2011 until last measurement at Mei 2017 to six ceramic insulators with coating and six ceramic isolators without coating. During aging time the insulators are given stress by AC voltage 50 Hz of 11 KV. During aging, data have been taken periodically in the form of leakage current data, contact angle, THD, and surface temperatur of the insulator. Data retrieval was conducted three times, ie morning afternoon and evening because the average humidity and temperature in each condition has different characteristics so that it can be known on what condition isolator flashover experience are easily obtained. From the data in the form of leakage current wave can then be determined the harmonic components for further analysis of the insulator characteristics.


After both types of insulators have aged for 5 years 7 months, researchers conducted a test to determine the performance of the insulator in the condition of clean fog and salt fog with the increase in voltage. From the result, along clean fog testing both insulators did not experience flashover. While in the test with salt fog, non-coating insulator experience flashover at 50 kV voltage and coated insulator have higher flashover voltage that is 60 kV.


To find out changed parameters during aging, simulations are performed on the measurement data in the field parameters are amplitude, waveform and THD of leakage current insulators during aging. Based on the test results, it is found that the use of coatings can increase performance of the ceramic insulator.

Copyrights : Copyright (c) 2001 by Perpustakaan Digital ITB. Verbatim copying and distribution of this entire article is permitted by author in any medium, provided this notice is preserved.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTITBPP
OrganisasiS
Nama KontakUPT Perpustakaan ITB
AlamatJl. Ganesha 10
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon62-22-2509118, 2500089
Fax62-22-2500089
E-mail Administratordigilib@lib.itb.ac.id
E-mail CKOinfo@lib.itb.ac.id

Print ...

Kontributor...

  • Pembimbing : Prof. Dr. Ir. Suwarno, MT, Editor: Alice Diniarti

File PDF...