ANALISIS GENERATOR SINKRON BELITAN GANDA TIGA FASA DENGAN BEBAN PENYEARAH JEMBATAN DUA BELAS PULSA

Master Theses from JBPTITBPP / 2017-09-27 15:37:38
Oleh : AYONG HIENDRO (NIM 23298019); Pembimbing: Prof. H.T.M. Soelaiman, M.SEE., dan Dr.Ir. Pekik Argo Dahono, S2 - Electrical Engineering
Dibuat : 2000, dengan 8 file

Keyword : generator sinkron belitan,ganda tiga fasa,penyearah jembatan dua belas pulsa.
Subjek : Electrical Engineering
Kepala Subjek : Engineering
Nomor Panggil (DDC) : T 621.313 4 HIE
Url : http://otomasi.lib.itb.ac.id/home.php?menu=library&action=detail&libraryID=73974
Sumber pengambilan dokumen : 20060848

Penelitian dilakukan untuk mengamati dan menganalisis kinerja generator belitan ganda tiga fasa ketika dibebani dengan penyearah jembatan dua belas pulsa. Model untuk simulasi dibuat dan diuji dengan eksperimen terhadap mesin yang sesungguhnya di dalam laboratorium. Hasil simulasi model menunjukkan kecocokan dengan hasil pengujian. Model tersebut dipergunakan untuk menganalisis kinerja generator dengan melihat pengaruh hubungan penyearah, titik netral, beda fasa dua set belitan stator, belitan peredam dan trafo interfasa (untuk penyearah hubungan paralel).

Hasil yang diperoleh menunjukkan hubungan rangkaian penyearah jembatan (seri atau paralel) mempengaruhi besar distorsi tegangan dan arus keluaran generator serta riak keluaran dc. Penyatuan titik netral memperburuk kinerja generator dan meningkatkan riak keluaran dc. Beda fasa antara dua set belitan stator untuk generator dibebani penyearah jembatan dua belas pulsa yang dapat menghasilkan distorsi tegangan keluaran generator yang minimum adalah sebesar 30 derajat listrik. Salah satu cara mengurangi THD tegangan dan arus keluaran generator dapat dilakukan dengan menghilangkan belitan peredam generator. Penggunaan trafo interfasa dalam penyearah jembatan paralel dapat mengurangi THD tegangan dan arus keluaran generator serta memperhalus riak keluaran dc, namun memperlambat transien dan menurunkan besar tegangan dc keluaran penyearah.

Deskripsi Alternatif :

Research is done to observe and analyze performance of a double three phase synchronous generator with twelve-pulse bridge rectified output. A model for simulation is developed and validated with experimental results obtained from actual machine in laboratory. The results of the simulation model are in very good agreement with the test results. The model is used to analyze the performance of the machine predicted from influence of rectifier bridges connection, neutral connection, phase shift between two set stator windings and interphase transformer (for parallel bridge connection).

The results obtained show that rectifier bridge connection (in series or in parallel) affect to the deformation of generator ac output voltage and current, also to the dc voltage ripple. Unity the neutral deforms the performance of the machine and increase the dc output ripple. Displacement angle between two set stator windings for the generator with twelve-pulse bridge rectified output for minimum voltage harmonic distortion occurs at 30 electrical degree. The generator output voltage and current THD can be reduced by eliminating generator damper windings. Parallel operation of two six-pulse bridge rectifiers with interphase transformer can reduce generator output voltage and current THD and make dc output ripple smoother, but in contrary oscillation takes place in larger time constant and decrease the value of rectifier dc output voltage.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTITBPP
OrganisasiS
Nama KontakUPT Perpustakaan ITB
AlamatJl. Ganesha 10
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon62-22-2509118, 2500089
Fax62-22-2500089
E-mail Administratordigilib@lib.itb.ac.id
E-mail CKOinfo@lib.itb.ac.id

Print ...

Kontributor...

  • Pembimbing: Prof. H.T.M. Soelaiman, M.SEE., dan Dr.Ir. Pekik Argo Dahono, Editor: Vika A. Kovariansi

File PDF...